During the previous two days, the company's colleagues had been assisted in installing a fireproof door, which they had returned to triangulate and share for information and communication。
Let's start with the word "extra"
At noon, he had a chat with the head of fire safety, who said that the fire brigade had come to check earlier, without a fine, and that the “drinking table” had been changed to a deadline. Leadership: "drink is a good thing, as long as you say it beautifully, you give each other a reason to drink, you're happy, you're happy, you're happy."
The joke is a joke, and the fire doors can be effective at critical times in halting the spread of fires, keeping them in the area of fire and buying valuable time for evacuation and fire rescue。

Why does the archives need fire doors
I came back to look at the rules and didn't find a separate mandatory provision for the "archive room" to install fire doors. It may be that there is a large amount of paper in the archives and that there is a high risk of fire, which is dealt with on the basis of “critical sites”。
Fire protection doors fire resistance summary
Level
Fire tolerance limits
Common scenes
Level a
≥1. 50h
Firewalls, fire pump room, transformer room, boiler room, etc
Level b
≥1. 00h
Evacuate stairwells, asylum lanes, public residential walkways, etc
Level c
≥0. 50h
Inspection doors vertically to wells (cables, pipelines)
Armoured fire doors
Serial number
Set part
Normative provisions
The doors on the firewall, the evacuation lanes in the fire zone. The door
Article 6. 4. 2
The door on a firewall with a fire tolerance limit of not less than 3. 00h
Gates between elevators, evacuation stairs and garages
Indoor exits to the front door of the asylum tunnel, the refuge room the door
Smoke-proof stairwells when underground or semi-subsurface stores are connected to adjacent areas the door
Article 5. 3. 5 of gb50016-2014 (2018 edition)
Theaters, cinemas, auditoriums separated from other areas in civilian buildings the door
Gb50016-2014 (2018 edition) article 5. 4. 7
Fuel/gas boiler room, transformer room, diesel generator room, storage room, etc. The door
Gb50016-2014 (2018 edition) articles 5. 4. 12, 5. 4. 13
Ports of the c liquid intermediate storage tank/middle tank room (including plant and civil buildings)
Gb50016-2014 (2018 ed.) articles 3. 3. 7, 5. 4. 14
Level-b fire gate
The door on the wall in the office and lounge in the c factory
Gb50016-2014 (2018 edition) art. 3. 3. 5
Offices, lounges, wall doors in c, d
Article 3. 3. 9 of gb50016-2014 (2018 edition)
A., b., multi-storey c, densely populated public buildings and other high-level industrial and civilian buildings between closed stairs
Gb55037-2022 article 6. 4. 3
Smoke-proof stairwells and front doors, fire elevator front rooms or shared front rooms the door
Gb55037-2022 paras. 6. 4. 3
In the front room, open the door to the escape route and evacuate the stairs from the inside to the outside. The door
The door on a firewall with a fire-resistant limit of not less than 2. 00h
Room evacuation in the entertainment show. The door
The door on the wall of the care unit in the wards of hospitals and nursing homes
Article 5. 4. 5 of gb50016-2014 (2018 edition)
Fire control room doors (fire control rooms attached to buildings should be separated from other parts by fire protection doors, windows, fireproof walls with a fire resistance limit of not less than 2. 00h, and floors with a fire resistance threshold of not less than 1. 50h)
Articles 4. 1. 8, 6. 4. 3
There's a mall on both sides of the street facing the door
Article 5. 3. 6 of gb50016-2014 (2018 edition)
Level c firegate: single but clear
Gb55037-2022 art. 6. 4. 5: the inspection door shall be a level c fireproof door for cable wells, pipeline wells, etc., vertically on the wall of the wellway。
Firegate connection control
In accordance with article 4. 6. 1 of the code for the design of an automatic fire alert system gb50116-2013:
Trigger signal: within the fire sub-area where the fire door is frequently opened, two separate fire detectors or one detector + a signal from a manual alarm button, which is a trigger signal from a connection that is frequently closed from the fire gate, shall be fired by the fire alarm controller or the fire link controller, and shall be operated by the fire link controller or the fire gate monitor to control the door from the fire。
State feedback: the opening, closing and failure of all fire doors on the evacuation route must be fed in real time to the fire doors monitor to ensure that the management side is clear。
Final focus
Level a is used mostly for equipment rooms, level b for walkways stairwells, level c pipes well
Fire inspection and acceptance assessments focused on door identification, sequencers, shutters, swelling seals。