    Key Point:Talk about fire suppression equipmentI'm sure the first thing you think about is fire extinguishersBut all alongMost people don't understandHow the fire extinguishers were regularly repaired and maintainedI'll show you today3+1 and 5+2 in fire extinguisher maintenanceWhile fire extinguishers are purchased as more common fire-fighting equipment, enterprises, units, families, etc., it is important not to assume that the purchase of fire extinguishe

    Talk about fire suppression equipment

    I'm sure the first thing you think about is fire extinguishers

    But all along

    Most people don't understand

    How the fire extinguishers were regularly repaired and maintained

    I'll show you today

    “3+1” and “5+2” in fire extinguisher maintenance

    Fire extinguisher maintenance period

    While fire extinguishers are purchased as more common fire-fighting equipment, enterprises, units, families, etc., it is important not to assume that the purchase of fire extinguishers is highly desirable and that they will not be used at an emergency time without timely maintenance and functional inspections, resulting in increased fire and even casualties。

    Duration of fire extinguishers

    There are two aspects to the validity of the fire extinguisher: one is the fire extinguisher, and the state establishes a mandatory end-of-life period for the fire extinguisher; the other is that the fire extinguisher in the fire extinguisher has its own validity, which is what we call the maintenance year。

    Fire extinguisher maintenance period

    The duration of maintenance varies according to the type of fire extinguisher. The water-based fire extinguisher should be repaired for the first time in three years after the end of the plant and every year after the first security check, that is, “3+1”。

    3+1

    Fire extinguisher maintenance period

    Hand-held dry powder extinguishers and hand-held carbon dioxide extinguishers should be repaired for the first time five years after the end of the plant, and every two years after the first repair should be sent for maintenance to a unit with a level iii maintenance and preservation qualification, that is, “5+2”. It should be noted that the driver dry powder extinguisher and pusher carbon dioxide extinguisher were first repaired for three years after they had expired, and then every year after that。

    5+2

    Fire extinguisher maintenance period

    Fire extinguisher maintenance period

    Review of fire extinguishers

    Appearance check

    Increments: examination of whether the fire extinguisher contains rust, deformation, disfigurement or cracks. Fire extinguishers shall be treated as scrap if the area of the fire extinguisher is more than one third rusted, equal to the total area of the cartridge, if there is a puddle on the surface, or if there is a visible disfigurement of the cartridge or serious mechanical damage。

    Insurance sales and lead seals: check the sale of hand-held fire extinguishers and the integrity of the lead seals to ensure that they are not opened or damaged。

    Nozzles and jet hoses: see if the nozzles are deformed, fractured, damaged, vent hoses are unbroken, deformed and damaged, and if there is a problem, replacement is required in time to ensure that the fire extinguisher is properly sprayed。

    Metals such as presses, valves, etc.: checks whether the fire extinguishers, valves, etc. Have severe damage, deformation, rust, etc. Defects in use。

    Rubber, plastics: to check whether the fire extinguisher's rubber, plastics are deformed, coloured, ageing or fractured, such as pressure valves, sealing pads, etc., should be replaced in a timely manner to avoid compromising the sealing and normal use of fire extinguishers。

    Pressure check

    Check if the outer surface of the fire extinguisher pressure table is deformed or damaged, if the pointer is in the green zone and if the pointer is in the red area, indicating that the fire extinguisher pressure is insufficient, it needs to be inflated or replaced in a timely manner; if the pointer is in the yellow area, indicating that the pressure is excessive and can be used normally, but the risk of explosion or explosion requires special attention and appropriate treatment。

    Fire extinguishers and gas inspection

    Quality and quantity of fire extinguishers: to check the adequacy of fire extinguishers, the absence of blocks, deterioration or contamination, such as dry powder extinguishers, check whether dry powder is humid and, if any, replace them in a timely manner; for carbon dioxide extinguishers, the gas cylinders are to be removed semi-annually, stating that the weight of the carbon dioxide in the cylinders, the leakage of the portable fire extinguisher's carbon dioxide cylinders is greater than 5 per cent or 7 g of the nominal weight, and if the pusher's carbon dioxide leakage is greater than 10 per cent。

    Driver gas pressure: ensure that the driving gas pressure is normal to ensure that fire extinguishers are properly sprayed。

    Spray performance test

    Simulation spray tests are conducted to check whether the fire extinguisher's injection is smooth, the distance, the duration and the trajectory of the spraying are in accordance with the prescribed requirements, and if they are not, the causes are identified and repaired in a timely manner to ensure an effective fire suppression function at the time of the fire。

    Other inspections

    Operating bodies: check the flexibility of the operating agencies, the tightness of the seals and the rigidity of the fire extinguisher covers。

    Components such as powder-producing tubes, gas intake tubes: check whether the fire extinguisher has been plugged in, including in, in, nozzles, nozzles and nozzles, whether the powder-deficit membranes, nozzles have been broken or broken, and find that the jam should be cleaned up in time and that the antitidal membranes and nozzles should be replaced in time。

    Fire extinguisher maintenance period

    What kind of fire extinguisher needs repair

    Once the fire extinguisher is opened, it must be refilled. In the event that rust, ageing, pressure (mechanical damage, visible rust, leaking of fire extinguishers, fire extinguishers opened for use or otherwise eligible for maintenance) are discovered during normal times, repairs should be carried out in a timely manner。

    Fire extinguisher maintenance period

    Fire extinguisher maintenance attention

    Not only should the maintenance and refilling of fire extinguishers be carried out by professional units that have obtained a maintenance permit, but, in order to ensure safety, the number of fire extinguishers sent out should not exceed one quarter of the total number of fire extinguishers. In excess, a fire extinguisher of the same type and method of operation shall be selected and the fire extinguisher of the fire extinguisher shall not be less than the fire extinguisher of the original fire extinguisher。

    Fire extinguisher maintenance period

    Fire extinguisher maintenance period

    In order to ensure the safe use of fire extinguishers, it is possible to combat initial fires in a timely and efficient manner, minimize fire hazards and protect persons and property. The fire extinguishers are regularly repaired and maintained at home and are not pre-empted。

    Fire extinguisher maintenance period

    Source: zheng dong ning fire and rescue team. Ice-freeze. Contents

     