    Key Point:During the previous two days, the company's colleagues had been assisted in installing a fireproof door, which they had returned to triangulate and share for information and communication。Let's start with the word "extra"At noon, he had a chat with the head of fire safety, who said that the fire brigade had come to check earlier, without a fine, and that the drinking table had been changed to a deadline. Leadership: "drink is a good thing,

    During the previous two days, the company's colleagues had been assisted in installing a fireproof door, which they had returned to triangulate and share for information and communication。

    Let's start with the word "extra"

    At noon, he had a chat with the head of fire safety, who said that the fire brigade had come to check earlier, without a fine, and that the “drinking table” had been changed to a deadline. Leadership: "drink is a good thing, as long as you say it beautifully, you give each other a reason to drink, you're happy, you're happy, you're happy."

    The joke is a joke, and the fire doors can be effective at critical times in halting the spread of fires, keeping them in the area of fire and buying valuable time for evacuation and fire rescue。

    Electronic locking of fire doors

    Why does the archives need fire doors

    I came back to look at the rules and didn't find a separate mandatory provision for the "archive room" to install fire doors. It may be that there is a large amount of paper in the archives and that there is a high risk of fire, which is dealt with on the basis of “critical sites”。

    Fire protection doors fire resistance summary

    Level

    Fire tolerance limits

    Common scenes

    Level a

    ≥1. 50h

    Firewalls, fire pump room, transformer room, boiler room, etc

    Level b

    ≥1. 00h

    Evacuate stairwells, asylum lanes, public residential walkways, etc

    Level c

    ≥0. 50h

    Inspection doors vertically to wells (cables, pipelines)

    Armoured fire doors

    Serial number

    Set part

    Normative provisions

    The doors on the firewall, the evacuation lanes in the fire zone. The door

    Article 6. 4. 2

    The door on a firewall with a fire tolerance limit of not less than 3. 00h

    Gates between elevators, evacuation stairs and garages

    Indoor exits to the front door of the asylum tunnel, the refuge room the door

    Smoke-proof stairwells when underground or semi-subsurface stores are connected to adjacent areas the door

    Article 5. 3. 5 of gb50016-2014 (2018 edition)

    Theaters, cinemas, auditoriums separated from other areas in civilian buildings the door

    Gb50016-2014 (2018 edition) article 5. 4. 7

    Fuel/gas boiler room, transformer room, diesel generator room, storage room, etc. The door

    Gb50016-2014 (2018 edition) articles 5. 4. 12, 5. 4. 13

    Ports of the c liquid intermediate storage tank/middle tank room (including plant and civil buildings)

    Gb50016-2014 (2018 ed.) articles 3. 3. 7, 5. 4. 14

    Level-b fire gate

    The door on the wall in the office and lounge in the c factory

    Gb50016-2014 (2018 edition) art. 3. 3. 5

    Offices, lounges, wall doors in c, d

    Article 3. 3. 9 of gb50016-2014 (2018 edition)

    A., b., multi-storey c, densely populated public buildings and other high-level industrial and civilian buildings between closed stairs

    Gb55037-2022 article 6. 4. 3

    Smoke-proof stairwells and front doors, fire elevator front rooms or shared front rooms the door

    Gb55037-2022 paras. 6. 4. 3

    In the front room, open the door to the escape route and evacuate the stairs from the inside to the outside. The door

    The door on a firewall with a fire-resistant limit of not less than 2. 00h

    Room evacuation in the entertainment show. The door

    The door on the wall of the care unit in the wards of hospitals and nursing homes

    Article 5. 4. 5 of gb50016-2014 (2018 edition)

    Fire control room doors (fire control rooms attached to buildings should be separated from other parts by fire protection doors, windows, fireproof walls with a fire resistance limit of not less than 2. 00h, and floors with a fire resistance threshold of not less than 1. 50h)

    Articles 4. 1. 8, 6. 4. 3

    There's a mall on both sides of the street facing the door

    Article 5. 3. 6 of gb50016-2014 (2018 edition)

    Level c firegate: single but clear

    Gb55037-2022 art. 6. 4. 5: the inspection door shall be a level c fireproof door for cable wells, pipeline wells, etc., vertically on the wall of the wellway。

    Firegate connection control

    In accordance with article 4. 6. 1 of the code for the design of an automatic fire alert system gb50116-2013:

    Trigger signal: within the fire sub-area where the fire door is frequently opened, two separate fire detectors or one detector + a signal from a manual alarm button, which is a trigger signal from a connection that is frequently closed from the fire gate, shall be fired by the fire alarm controller or the fire link controller, and shall be operated by the fire link controller or the fire gate monitor to control the door from the fire。

    State feedback: the opening, closing and failure of all fire doors on the evacuation route must be fed in real time to the fire doors monitor to ensure that the management side is clear。

    Final focus

    Level a is used mostly for equipment rooms, level b for walkways stairwells, level c pipes well

    Fire inspection and acceptance assessments focused on door identification, sequencers, shutters, swelling seals。

    I'm zhao liang for the rest of my life. Please comment on the zone! I thought it would help you

     