Not long ago
The sichuan people's government announced
Sichuan's "7-17" big fire
Accident investigation report
We've got a video of a public place
And the witness's phone
Interviews with accident-related persons and with fire scenes
It was combed and restored
Fire causes, contagion and disaster
Accident review
On 17 july 2024, at more than 6 p. M., fire broke out in the nine-ding building of the city of kamong city in sichuan province, and firefighters arrived at the scene and quickly formed multi-road fire relief units from various corridors into the firehouse。

At 10. 20 p. M. The fire was extinguished and the firefighters relocated 91 persons trapped from inside the fire building, of whom 16 were killed, 39 were injured and 5929 square metres were overfired。
Direct causes

The fire was the direct result of a group of undocumented workers approached by a waste recycler, who used liquefied gas to cut the escalators, when high-temperature slag fell on a small storehouse built in a supermarket in violation of the law, where a large number of boxes of clothing were stacked, and when high-temperature slags ignited combustible materials such as boxes, clothing, etc。
Revert the fire into disaster
The accident investigation team is collecting
The witness's phone was shot
Videos of surrounding public places
It was combed and restored
Fire, spread, disaster
On 17 july 2024, at more than 1800 hours, people at the nine ding building were shopping in supermarkets, and the 5th floor pool hall and the 6th floor teahouse were in regular business, gathering a large number of customers。
At 1808 hours and 37 seconds, the curtains behind the “recreational foods” section of the supermarket show a slight sparkling of fire in the storeroom。
At 1810 hours and 20 seconds, the supermarket internal emergency radio broadcasted the fire, warning people to evacuate in time. A woman in a blue short sleeve who heard the emergency broadcast and sensed abnormalities, went to the fire, and immediately called for evacuation when she opened the curtain。

At this point, a large amount of smoke began to gather in the storeroom. If the supermarket employees had used fire extinguishers at that time, they would have kept the fire in the warehouse, but they did not. The plume of smoke came out of the gap in the warehouse and spread to other regions, quickly filling the supermarket。

With the effect of the negative 1st to 5th floors of the middle court chimneys, just over two minutes of time, the fire became uncontrollable and rapidly spread along the courtyard to the 5th floor table hall, and, as a result of the frequent opening of the fireproof door in the stairs between the 5th and 6th floors, the fire spread to the 5th floor along the courtyard, soon erupted from the entry and exit of the 6th floor tea restaurant。

Soon the smoke broke through the window below the building, and people fled the other side of the corridor along the platform. People on the sixth floor of the teahouse quickly stormed the smoked area and set up a temporary platform along the stairs to escape。

There were signs of fire on the negative 1st to 6th floors
Where's the fire
Through on-site investigations
The investigation team will soon be eliminated
Fire, electrical, spontaneous combustion, smoking, etc
So, what's the reason
This fire
It is understood that prior to the incident, the owner of the supermarket, wang and the day-to-day manager of the nine ding group had agreed to move the supermarket from the negative 1st floor to the upper 1st floor of the floor and to expand the area of operation. Subsequently, the nine ding group sought liu xiaohian, who was involved in the acquisition of waste products, and liu was temporarily approached by a number of individuals to carry out the demolition of the partial escalator and the eight fire-proof curtains in the first courtyard. None of the temporarily recruited demolition and construction workers were trained or certified to be operational and were less aware of fire safety precautions。

The escalators were removed from the cutting worker liu jie-jian: not once. I told him. I didn't open the elevator。
Thus, in the absence of authorization for fire operations, several people who had no knowledge of the infrastructure of the escalators and had no experience of disassembly temporarily built a grass-roots team to begin the brutal and blind dismantling operations。

The investigation found that the cutting was in the course of operations, that there were no protective measures at the site, that there was no clean-up of the flammable materials around the site, that there were insufficient fire suppression equipment and the installation of site safety officers, that the high-temperature slag resulting from the cutting had led to the repeated combustion of flammable materials such as oil stains and side-packed planks below the escalators, and that the construction personnel had used only a tub of water。

And this time, the fire was a negative storehouse below the cutting point。
According to wang tian shwe, commander-in-chief of the fire department of the national fire and rescue agency, at the point where the workers were cutting the escalators, and just above the hole, a large number of high-temperature slags fell directly on the flammable material, such as clothing, paper, and so on, next to the post in the small warehouse, and the flame spread rapidly around it。

After a comprehensive analysis, the reasons for the fire were determined to be: the removal of the escalators by the non-eligible members of the group, the lack of security management of the use of the open fire, the brutal construction of the work by the operators, the spilling of high-temperature slags into a negative layer of the middle ladder, the supermarket room below the escalators, and the fire caused by the burning of the piles of clothing, boxes, etc。
What factors contribute to the rapid spread of fire
Investigation findings
After the cutter found the fire
Dry powder extinguishers and a small amount of water
He fled the scene without putting out the fire
No first call to 911
And notify 9d building property management
When the supermarket employee found out
Organize evacuation and call the police
But there was no first fire
Delayed optimal disposal time

On fire
There's only one guard in the nine ding building
And fire control room duty was present
There's no organization to save the first fire
The fire spreads rapidly inside the building

Negative first floor supermarket roof
Irregular use of flammable paint plates
This colored steel plate
Polystyrene material added to the middle
Burn speed

The investigation team also found that the fire-fighting facilities of the fire-fighting building were not connected and that some of the building's central fire-proof curtains had been removed and others had not decreased, thus causing damage to the security line, leaving the building, which was in operation, undefensible, unstopped by the pyrotechnic fire and spreading from the courtyard to other regions。

In further investigations, the investigation team learned that:
In the course of its construction, the building has been subjected to numerous random redundancies and irregularities in the construction and content of fire safety, resulting in a lack of conformity of the building size to the level of security, creating a “generic” hazard and increasing the risk of fire。
In addition, in the case of construction, outside decorative improvements and fire-fighting improvements, the enterprises concerned have not declared themselves in accordance with the law, and the lack of supervision of the source of the renovation works has created new “generic” risks。
The combination of factors has further reduced safety standards for building fire safety, resulting in major problems。
Why is it on fire
What happened to 16 people on the 5th floor
Numerical simulations show that, more than four minutes after the fire, the average temperature in the 2nd floor of the building was 500°c; the maximum temperature in the five floors of the building was 150°c, 200°c and 124°c, respectively, above the adult tolerance threshold of 60°c. Large amounts of high-temperature toxic smoke spread rapidly to the building floors as a result of the chimney effect。

Why did the fire on the first floor kill 16 people on the fifth floor
After the fire, the mechanized smoking system in the courtyard was not activated, and the automatic fire alarm system was not activated. As a result, the people on the 5th floor of the pool hall did not know that the fire was approaching them step by step
As can be seen from videos from public places, people on the 5th floor of the billiard hall found smoke and did not immediately evacuate the escape, but were on the lookout, thereby depriving them of the best opportunity to evacuate the escape。
The absence of seals on the top of the fire-proof curtain between the five-story pool hall and the courtyard, the gap between the wall and the roof, and the absence of a smoke-discharge facility in the pool hall, have resulted in a rapid influx of smoke that cannot be discharged, and the high temperature and toxic smoke directly encirclements the entire pool hall。

The fact that the staff opened the door was not closed, and the continuing influx of toxic, high-temperature smoke was also an important cause of death in the pool hall. Source: china news, chinese fireworks editor: li jamin